150KW 400V AC Resistive load bank

  • 1. Rated power: 150KW
  • 2. Rated voltage: 400V AC 3 Phase
  • 3. Control method: Local or remote
  • 4. Cooling method: Air force cooling
  • Product description: 150KW 400V AC Resistive load bank for generator test, total 14 steps with loca and remote control.
  • INQUIRY

150KW 400V AC Resistive Load banks apply the load to an electrical power source and dissipate the power of the electrical source. 


Item

Specification

Rated Voltage

AC400V Star Connection

Load type

Resistive, PF=1.0

Rated Power

150KW(Ue=380V

Rated Current

217A

Steps

Total 14 steps, 4×25KW10×5KW

Resistance Tolerance

≤5%

Control Method

Local: Button

RemoteRS485(MODBUS RTU)

Panel function button

Steps switch, power on/off button, Local/Remote Switch, Buzzer, Emergency stop button.

Resistor element

Alloy Resistor Element

Cooling method

Force air cooling, Front in/Back out

Fan power supply: AC 220V/50Hz

Power Frequency withstand voltage

AC2000V/50Hz, 1min, No breakdown and no blink

Testing Function

Three-phase voltage, current, active power, reactive power, apparent power, frequency, power factor and other parameters;

Display parameter resolution

0.1V/0.1A/0.1KW/1HZ

Working mode

Continuously working

Power Supply

3 Phase AC380V/50Hz

Protection

Over load protection; Over current protection; Emergency stop protection; Over temperature protection

Port

Load Bus; Power Supply; RS485 ;PE GND

Working Temperature

-10 55

Altitude

≤2000m

Relative humidity

The daily average is not more than 95%, the monthly average is not more than 90%, no condensation occurred;

Installation environment

Indoor, IP23

Estimated Dimension

Length=1000mmHeight=900mmDepth=1200mm

Weight

≈400KG 

Color

White or Gray

Insulation grade

F grade

Transportation

Vertical cabinet with casters; Wooden case package

Load Extension

1+N load boxes are available to extend in parallel